BIOFIL outlet filter 2 months
Removable BIOCLIP outlet, anti-legionella and antibacterial for specific use.
To be installed in place of the removable BIOCLIP outlet (without tools or shutting off the water supply).
Membrane type: tubular microfiltration.
Membrane material: Polyethylene.
Filtration degree: 0.1 µm nominal, sterilization grade.
Water volume per service life: 6000 liters.
Filter flow rate: 6 l/min at 3 bar (filter only, without flow restrictor in the tap).
Maximum inlet pressure: 5 bar.
Maximum service life: 2 months after installation.
Suitable for and resistant to thermal and chemical disinfections.
Non-sterile filter.
Weight: 40 g.
Reference for a single piece. Orders must be placed in multiples of 10.
Packed by 10 in a box.
| Technology | End-of-line filter |
| Length | 138 mm |
| Flow rate | 6L/min |
| Standards and certificates |
|
Specifications
| Article number | 814630040 |
|---|---|
| Brand | Delabie |
| Weight | 0.065 kg |